Home / Projects / Borno hubs / Dikwa

Case study · Humanitarian hub · Dikwa, Borno State

Solar hybrid power for a humanitarian hub in Dikwa

75 kWp of solar and 614.4 kWh of storage for a humanitarian hub in Dikwa, sized from what we saw at the hub.

Solar

75 kWp

Battery storage

614.4 kWh

Air conditioners

About 27

Commissioned

Feb 2025

Rooftop solar panels at a humanitarian hub in Borno State

Rooftop solar at one of the eight Borno hubs.

What it powers at the humanitarian hub in Dikwa

Dikwa is a regional office with guest rooms for humanitarian staff, and it's growing. It runs about 27 air conditioners, plus water heaters, kitchen equipment, fridges and freezers, lighting and internet.

How we split the loads

We wired the hub into two circuits, so the things that matter most never go off.

Critical loads: always on

Lights, fans, computers, internet, fridges and security run on the battery 24 hours a day.

Heavy loads: smart control

Air conditioners, water heaters and kitchen equipment switch off when the battery drops to 40% and come back on at 60%.

What we did

✓  Installed 120 JinkoSolar bifacial panels on the hub roofs
✓  Installed 2 Deye 50 kW hybrid inverters and 10 battery racks in a temperature-controlled power room
✓  Ran the system at full load for 48 hours before handover
✓  Trained the hub team to run and check the system

Full equipment list

•  75 kWp: 120 × JinkoSolar 625 Wp bifacial panels
•  100 kW inverter capacity: 2 × Deye 50 kW high-voltage hybrid inverters
•  614.4 kWh storage: 10 × Deye 61.44 kWh high-voltage battery racks
•  Off-grid hybrid with generator backup
•  Remote monitoring on DeyeCloud

Brands used: Deye · JinkoSolar

How the load control works

We sorted every circuit in the hub with the client's technical team. Critical loads sit on the battery circuit and never go off. Heavy loads sit on a separate, controlled circuit. The system runs everything from full battery down to 40%. At 40%, it switches the heavy loads off and waits for the next morning sun. At 60%, it turns them back on. The generators stay as a manual backup, so the hub team can see and manage how much energy the hub uses.

Running a facility on generators?

Tell us about your loads. We'll visit, measure and size a system that keeps the important things on.

Scroll to Top